function block in which systems, equipment or functions should receive this
information.
More specifically, DPGAPC function reports a combined double point position
indication output POSITION, by evaluating the value and the timestamp attributes
of the inputs OPEN and CLOSE, together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs
determine the two-bit integer value of the output POSITION. The timestamp of the
output POSITION will have the latest updated timestamp of the inputs OPEN and
CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to
intermediated state.
When the value of the input signal VALID changes, the timestamp of the output
POSITION will be updated as the time when DPGAPC function detects the
change.
Refer to Table
for the description of the input-output relationship in terms of the
value and the quality attributes.
Table 36:
Description of the input-output relationship
VALID
OPEN
CLOSE
POSITION
Value
Description
0
-
-
0
Intermediate
1
0
0
0
Intermediate
1
1
0
1
Open
1
0
1
2
Closed
1
1
1
3
Bad State
12.8.3
Setting guidelines
SEMOD55398-5 v4
The function does not have any parameters available in the local HMI or PCM600.
12.9
Single point generic control 8 signals SPC8GAPC
SEMOD176448-1 v3
12.9.1
Identification
SEMOD176456-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single point generic control 8 signals
SPC8GAPC
-
-
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
335
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...