In an intertrip scheme, the send signal is initiated by an underreaching zone or from
an external protection (transformer or reactor protection). At the remote end, the
received signals initiate a trip without any further protection criteria. To limit the
risk for an unwanted trip due to the spurious sending of signals, the timer
tCoord
should be set to 10-30 ms dependant on the type of communication channel.
The general requirement for teleprotection equipment operating in intertripping
applications is that it should be very secure and very dependable, since both
inadequate security and dependability may cause unwanted operation. In some
applications the equipment shall be able to receive while transmitting, and
commands may be transmitted over longer time period than for other teleprotection
systems.
13.1.3
Setting guidelines
IP15021-1 v1
M13869-4 v4
The parameters for the scheme communication logic function are set via the local
HMI or PCM600.
Configure the zones used for the CS send and for scheme communication tripping
by using the ACT configuration tool.
The recommended settings of
tCoord
timer are based on maximal recommended
transmission time for analogue channels according to IEC 60834-1. It is
recommended to coordinate the proposed settings with actual performance for the
teleprotection equipment to get optimized settings.
13.1.3.1
Blocking scheme
M13869-8 v5
Set
Operation
On
Set
SchemeType Blocking
Set
tCoord
25 ms (10 ms + maximal transmission time)
Set
tSendMin
0 s
Set
Unblock
Off
(Set to
NoRestart if Unblocking scheme with no alarm for loss of guard is to be
used.
Set to
Restart if Unblocking scheme with alarm for loss of guard is to be used)
Set
tSecurity
0.035 s
13.1.3.2
Permissive underreaching scheme
M13869-25 v4
Set
Operation
=
On
Set
SchemeType
=
Permissive UR
Set
tCoord
= 0 ms
Set
tSendMin
= 0.1 s
Set
Unblock
=
Off
Set
tSecurity
= 0.035 s
Section 13
1MRK 506 375-UEN A
Scheme communication
348
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...