14.6
Configurable logic blocks
IP11009-1 v3
The configurable logic blocks are available in two categories:
•
Configurable logic blocks that do not propagate the time stamp and the quality
of signals. They do not have the suffix QT at the end of their function block
name, for example, SRMEMORY. These logic blocks are also available as part
of an extension logic package with the same number of instances.
•
Configurable logic blocks that propagate the time stamp and the quality of
signals. They have the suffix QT at the end of their function block name, for
example, SRMEMORYQT.
14.6.1
Application
GUID-F5D6F065-441B-4296-AC56-F4DC1F5487E3 v3
A set of standard logic blocks, like AND, OR etc, and timers are available for
adapting the IED configuration to the specific application needs. Additional logic
blocks that, beside the normal logical function, have the capability to propagate
timestamp and quality are also available. Those blocks have a designation
including the letters QT, like ANDQT, ORQT etc.
14.6.2
Setting guidelines
GUID-E6BD982D-9E47-4CC2-9666-6E5CABA414C0 v3
There are no settings for AND gates, OR gates, inverters or XOR gates as well as,
for ANDQT gates, ORQT gates or XORQT gates.
For normal On/Off delay and pulse timers the time delays and pulse lengths are set
from the local HMI or via the PST tool.
Both timers in the same logic block (the one delayed on pick-up and the one
delayed on drop-out) always have a common setting value.
For controllable gates, settable timers and SR flip-flops with memory, the setting
parameters are accessible via the local HMI or via the PST tool.
14.6.2.1
Configuration
GUID-D93E383C-1655-46A3-A540-657141F77CF0 v4
Logic is configured using the ACT configuration tool in PCM600.
Execution of functions as defined by the configurable logic blocks runs according
to a fixed sequence with different cycle times.
For each cycle time, the function block is given an serial execution number. This is
shown when using the ACT configuration tool with the designation of the function
block and the cycle time, see example below.
1MRK 506 375-UEN A
Section 14
Logic
Railway application RER670 2.2 IEC
365
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...