For each of the 352 signals, it is also possible to select if the signal is to be used as
a trigger for the start of the Disturbance report and if the trigger should be activated
on positive (1) or negative (0) slope.
OperationN
: Disturbance report may trig for binary input N (
On
) or not (
Off
).
TrigLevelN
: Trig on positive (
Trig on 1
) or negative (
Trig on 0
) slope for binary
input N.
Func103N
: Function type number (0-255) for binary input N according to
IEC-60870-5-103, that is, 128: Distance protection, 160: overcurrent protection,
176: transformer differential protection and 192: line differential protection.
Info103N
: Information number (0-255) for binary input N according to
IEC-60870-5-103, that is, 69-71: Trip L1-L3, 78-83: Zone 1-6.
See also description in the chapter IEC 60870-5-103.
15.6.3.3
Analog input signals
M12179-92 v5
Up to 40 analog signals can be selected among internal analog and analog input
signals. PCM600 is used to configure the signals.
For retrieving remote data from LDCM module, the Disturbance
report function should be connected to a 8 ms SMAI function block
if this is the only intended use for the remote data.
The analog trigger of Disturbance report is not affected if analog input M is to be
included in the disturbance recording or not (
OperationM
=
On
/
Off
).
If
OperationM
=
Off
, no waveform (samples) will be recorded and reported in
graph. However, Trip value, pre-fault and fault value will be recorded and reported.
The input channel can still be used to trig the disturbance recorder.
If
OperationM
=
On
, waveform (samples) will also be recorded and reported in
graph.
NomValueM
: Nominal value for input M.
OverTrigOpM
,
UnderTrigOpM
: Over or Under trig operation, Disturbance report
may trig for high/low level of analog input M (
On
) or not (
Off
).
OverTrigLeM
,
UnderTrigLeM
: Over or under trig level, Trig high/low level relative
nominal value for analog input M in percent of nominal value.
15.6.3.4
Sub-function parameters
M12179-389 v3
All functions are in operation as long as Disturbance report is in operation.
1MRK 506 375-UEN A
Section 15
Monitoring
Railway application RER670 2.2 IEC
401
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...