EnaAcc
:
Off
/
On
is used to switch the accumulation of energy on and off.
tEnergy
: Time interval when energy is measured.
tEnergyOnPls
: gives the pulse length ON time of the pulse. It should be at least
100
ms when connected to the Pulse counter function block. Typical value can be
100
ms.
tEnergyOffPls
: gives the OFF time between pulses. Typical value can be
100
ms.
EAFAccPlsQty
and
EARAccPlsQty
: gives the MWh value in each pulse. It should
be selected together with the setting of the Pulse counter (PCGGIO) settings to
give the correct total pulse value.
ERFAccPlsQty
and
ERVAccPlsQty
: gives the MVArh value in each pulse. It should
be selected together with the setting of the Pulse counter (PCGGIO) settings to
give the correct total pulse value.
For the advanced user there are a number of settings for direction, zero clamping,
max limit, and so on. Normally, the default values are suitable for these parameters.
Section 16
1MRK 506 375-UEN A
Metering
414
Railway application RER670 2.2 IEC
Application manual