components and so on. This information is then used by the respective functions
connected to this SMAI block in the ACT (for example protection, measurement or
monitoring functions).
21.10.2
Frequency values
GUID-B494B93C-B5AA-4FD6-8080-8611C34C2AD8 v5
A valid input voltage signal level for frequency measurement can be set with
SMAI setting
MinValFreqMeas
in % of
UBase
. If the input signal level (positive
sequence or single phase voltage) is lower than the
MinValFreqMeas
level, then the
frequency output is invalid and the connected frequency functions will be blocked.
21.10.3
Setting guidelines
GUID-C8D6C88B-87C6-44C1-804B-CF1594365EE6 v8
The parameters for the signal matrix for analog inputs (SMAI) functions are set via
the local HMI or PCM600.
Application functions should be connected to a SMAI block with same task cycle
as the application function, except for e.g. measurement functions that run in slow
cycle tasks.
Negation
: If the user wants to negate the 2ph signal, it is possible to choose to
negate only the phase signals
Negate2Ph
, only the neutral signal
NegateN
or both
NeN
. Negation means rotation with 180° of the vectors.
GlobalBaseSel
: Selects the global base value group used by the function to define
(
IBase
), (
UBase
) and (
SBase
).
MinValFreqMeas
: The minimum value of the voltage for which the frequency is
calculated, expressed as percent of UBase (for each instance n).
A valid input voltage signal level for frequency measurement can be set with
SMAI setting
MinValFreqMeas
in % of UBase. If the input signal level (positive
sequence or single phase voltage) is lower than the
MinValFreqMeas
level, then the
frequency output is invalid and the connected frequency functions will be blocked.
Even if the user sets the
AnalogInputType
of a SMAI block to
“
Current
”, the
MinValFreqMeas
is still visible. However, using the
current channel values as base for frequency measurement is
not
recommendable
for a number of reasons, not last among them
being the low level of currents that one can have in normal
operating conditions.
The preprocessing block shall only be used to feed functions within
the same execution cycles. The only exceptions are the
measurement functions (CVMMXN, CMMXU,VMMXU, etc.).
1MRK 506 375-UEN A
Section 21
Basic IED functions
Railway application RER670 2.2 IEC
469
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...