7.1.3
Setting guidelines
M13855-4 v10
The parameters for automatic switch onto fault logic, voltage- and current-based
function ZCVPSOF are set via the local HMI or Protection and Control Manager
PCM600.
The distance protection zone used for instantaneous trip by ZCVPSOF has to be set
to cover the entire protected line with a safety margin of minimum 20%.
Common base IED values for primary current (
IBase
), primary voltage (
UBase
)
and primary power (
SBase
) are set in the global base values for settings function
GBASVAL.
GlobalBaseSel
is used to select GBASVAL for reference of base values.
Operation
: The operation of ZCVPSOF is by default set to
On
. The parameter must
be set to
Off
if ZCVPSOF is not to be used.
IPh<
is used to set the current level for the detection of a dead line.
IPh<
is, by
default, set to 20% of
IBase
. It shall be set with a sufficient margin (15–20%)
below the minimum expected load current. In many cases, the minimum load
current of a line is close to zero and even can be zero. The operating value must
exceed the maximum charging current of an overhead line when only one phase is
disconnected (mutual coupling in the other phases).
UPh<
is used to set the voltage level for the detection of a dead line.
UPh<
is, by
default, set to 70% of
UBase
. This is a suitable setting in most cases, but it is
recommended to check the suitability in the actual application.
AutoInitMode
: automatic activating of ZCVPSOF is, by default, set to
DLD
disabled
, which means the dead-line logic detection is disabled. If an automatic
activation of the dead-line detection is required, the parameter
AutoInitMode
has to
be set to either
Voltage
,
Current
or
Current & Voltage
.
When
AutoInitMode
is set to
Voltage
, the dead-line detection logic checks that the
two-phase voltages are lower than the set
UPh<
level.
When
AutoInitMode
is set to
Current
, the dead-line detection logic checks if the
two-phase currents are lower than the set
IPh<
level.
When
AutoInitMode
is set to
Current & Voltage
, the dead-line detection logic
checks that both two-phase currents and two-phase voltages are lower than the set
IPh<
and
UPh<
levels.
Otherwise, the logic is activated by an external
BC
input.
tSOTF
: the drop delay of ZCVPSOF is, by default, set to 1.0 seconds, which is
suitable for most applications.
Section 7
1MRK 506 375-UEN A
Impedance protection
96
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...