tDLD
: The time delay for activating ZCVPSOF by the internal dead-line detection
is, by default, set to 0.2 seconds. It is suitable in most applications. The delay shall
not be set too short to avoid unwanted activations during transients in the system.
Mode
: The operation of ZCVPSOF has three modes for defining the criteria for
tripping. The setting of
Mode
is, by default,
UILevel
, which means that the tripping
criterion is based on the setting of
IPh<
and
UPh<
. The choice of
UILevel
gives a
faster and more sensitive operation of the function, which is important for reducing
the stress that might occur when energizing onto a fault. However, the voltage
recovery can be slow in some systems when energizing the line. Therefore, if the
timer
tDuration
is set too short, ZCVPSOF can interpret this as a fault and release a
trip.
When
Mode
is set to
Impedance
, the operate criterion is based on the
BC
input
(breaker closing), which can be the start of the overreaching zone from the
impedance zone measurement. A nondirectional output signal should be used from
an overreaching zone. The selection of the
Impedance
mode gives increased
security.
When
Mode
is set to
UILvl&Imp
, the condition for tripping is an ORed between
UILevel
and
Impedance
.
tDuration
: The setting of the timer for the release of UILevel is, by default, 0.02
seconds, which has proven to be suitable in most cases from field experience. If a
shorter time delay is to be set, it is necessary to consider the voltage recovery time
during line energization.
7.2
Distance protection, quadrilateral characteristic
ZRWPDIS
GUID-5C7859F2-72C7-409D-8D6F-BCD7E9E18F52 v1
7.2.1
Identification
GUID-BAB9DF6F-B697-4C95-9548-3D86BF4D590D v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/
IEEEidentification
Distance protection, quadrilateral
characteristic
ZRWPDIS
Z<
IEC15000305 V1 EN-US
21
7.2.2
Application
GUID-3A97F695-7AB9-4049-8C3A-662B5CB4230F v2
The distance protection, quadrilateral characteristic ZRWPDIS function is
applicable for all earthing types in 2-phase power networks. The
SystemEarthing
setting is provided in order to have the distance protection function suitable for a
specific type of earthing system.
1MRK 506 375-UEN A
Section 7
Impedance protection
Railway application RER670 2.2 IEC
97
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...