TimerSelZ6
: This is used to set the zone timer selection mode of zone 6. i.e.
Timers
separated
,
Timers linked
,
General start
,
PhSel start
,
Internal start
and
External
start
. The default setting is
Timers separated
.
OpModetPEZ6
: This is used to set the
Off/On
operation of the phase-to-earth timer
of zone 6. The default setting is
Off
.
tPEZ6
: This is used to set the time delay to trip for phase-to-earth faults in zone 6.
It should be set to 0.0 s.
OpModetPPZ6
: This is used to set the
Off/On
operation of the phase-to-phase timer
of zone 6. The default setting is
Off
.
tPPZ6
: This is used to set the time delay to trip for phase-to-earth faults in zone 6.
It should be set to 0.0 s.
Phase Selection
GUID-62310709-49F4-4D60-869C-2145D574B459 v2
tI0
: Delay time for the residual overcurrent start. Residual overcurrent start is
delayed by settable time delay
tI0
. The default setting is 0.2s.
ModeU0DetMin
: This is used to enable/disable the neutral voltage shift protection.
The default setting is
Off
.
U0DetMin
: This is used to set the minimum operate value for the neutral voltage
shift. The default value is 20%
UB
.
UDisp
GUID-1885B794-9F95-446B-A656-0A37AAB7F193 v2
OpModeU0
: This is used for the
Off/On
operation of the neutral voltage
displacement logic. The default value is
Off
.
UMinDisp
: This is used to check the neutral voltage displacement for single phase-
earth-faults occur in the system. The default setting is 150%
UB
.
tU0
: This is the time delay to trip for the neutral voltage displacement start. The
default value is 5.0s.
7.2.3
Setting examples
7.2.3.1
Compensated earthed systems
GUID-C9010253-2D63-485B-ACF9-48166C03E017 v2
illustrates how the distance protection ZRWPDIS protects a
110kV overhead transmission line. The earthing considered is compensated earthed
system.
Out of the six distance protection zones, only the zone 1, zone 2 and zone 3 are
considered in this example. Zones 4, 5 and 6 can be set on similar lines depending
on the application they are being used.
All the settings for impedance are in Ohms Primary.
1MRK 506 375-UEN A
Section 7
Impedance protection
Railway application RER670 2.2 IEC
135
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...