Set value for the parameter
CurrentInput
Comment
MaxPh
1)
D2PTOC function will measure current of the
phase with maximum magnitude
phase1-phase2
D2PTOC function will measure the current
internally calculated as the vector difference
between the phase L1 current and phase L2
current
IL
IL
1) = Note that
MaxPh current selection shall not be used when D2PTOC function is used as
directional. It shall be only used when function is used for non-directional operation.
VoltageInput
: This is used to select the type of energizing quantity (i.e. phasor) for
voltage and will be used as polarizing signal to detect the direction of faults if any
of the two steps is set for Forward/Reverse mode of operation.
Table 18:
Voltage selection for D2PTOC function
Set value for the parameter
VoltageInput
Comment
phase1
D2PTOC function will measure the phase L1
voltage
phase2
D2PTOC function will measure the phase L2
voltage
PosSeq
D2PTOC function will measure internally
calculated positive sequence voltage
1
2 / 2
UL
UL
phase1-phase2
D2PTOC function will measure the voltage
internally calculated as the vector difference
between the phase L1 voltage and phase L2
voltage
UL
UL
For directional operation of the D2PTOC function, the identical
values for current and voltage measurement selection shall be set
(e.g. both set to
PosSeq
, or both set to
phase1
).
OperHarmRestr
: This is used to
Off
/
On
the 2nd harmonic restrain feature for the
D2PTOC function.
I_2nd/I_fund
: Operate level of 2nd harmonic current restrain set in % of the
fundamental current. The setting range is
10.0 - 50.0
% in steps of 1%. The default
setting is 20%.
RCADir
: Relay characteristic angle set in degrees. It defines the middle line of the
forward operating sector in the directional plane.
ROADir
: Relay operate angle value, given in degrees, to define the width of the
forward operating sector in the directional plane, shown in Figure
.
LowVolt
: This is used to set low-voltage level in % of
UBase
for the direction
detection. If measure voltage is below this set level, the setting
ActLowVoltx
(where
x = 1 & 2) decides the function behavior.
1MRK 506 375-UEN A
Section 8
Current protection
Railway application RER670 2.2 IEC
163
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...