The bus and line frequencies must also be within a range of ±10% from the
rated frequency. When the synchronizing option is included also for
autoreclose there is no reason to have different frequency setting for the
manual and automatic reclosing and the frequency difference values for
synchronism check should be kept low.
•
The frequency rate of change is less than set value for both U-Bus and U-Line.
•
The difference in the phase angle is smaller than the set value of
CloseAngleMax
.
•
The closing angle is decided by the calculation of slip frequency and required
pre-closing time.
The synchronizing function compensates for the measured slip frequency as well as
the circuit breaker closing delay. The phase angle advance is calculated
continuously. The calculation of the operation pulse sent in advance is using the
measured
SlipFrequency
and the set
tBreaker
time. To prevent incorrect closing
pulses, a maximum closing angle between bus and line is set with
CloseAngleMax
.
Table
below shows the maximum settable value for
tBreaker
when
CloseAngleMax
is set to 15 or 30 degrees, at different allowed slip frequencies for
synchronizing. To minimize the moment stress when synchronizing near a power
station, a narrower limit for the
CloseAngleMax
needs to be used.
Table 23:
Dependencies between tBreaker and SlipFrequency with different CloseAngleMax
values
tBreaker [s] (max settable value)
with
CloseAngleMax = 15
degrees [default value]
tBreaker [s] (max settable value)
with
CloseAngleMax = 30 degrees
[max value]
SlipFrequency [Hz]
(BusFrequency -
LineFrequency)
0.040
0.080
1.000
0.050
0.100
0.800
0.080
0.160
0.500
0.200
0.400
0.200
0.400
0.810
0.100
1.000
0.080
0.800
0.050
1.000
0.040
The reference voltage can be phase-neutral L1, L2 or positive sequence. By setting
the phases used for SESRSYN, with the settings
SelPhaseBus
and
SelPhaseLine
, a
compensation has to be made for the phase angle difference caused if different
setting values are selected for the two sides of the breaker. This compensation has
to be done with the
PhaseShift
setting according to Table
Section 12
1MRK 506 375-UEN A
Control
212
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...