Figure 73:
Example of I/O-signal connections at an auto reclosing sequence
12.2.3.2
Auto recloser settings
GUID-74980A07-CF89-488F-AB17-E5351D0032EE v1
The settings for the auto recloser are set using the local HMI (LHMI) or PCM600.
This setting guideline describes the settings of the auto recloser using the LHMI.
The settings for the auto recloser are found under
Main menu/Settings/IED
Settings/Control/AutoRecloser(79,5(0->1))/SMBRREC(79,5(0->)):X
and have
been divided into four different setting groups: General, CircuitBreaker, DeadTime
and MasterSlave.
General settings
Operation
: The operation of the auto recloser can be switched
On
or
Off
.
ExternalCtrl
: This setting makes it possible to switch the auto recloser On or Off
using an external switch via IO or communication ports.
StartByCBOpen
: The normal setting
Off
is used when the function is started by
protection trip signals. If set
On
the start of the auto recloser is controlled by an
circuit breaker auxiliary contact.
LongStartInhib
: Usually the protection trip command, used as an auto reclosing
start signal, resets quickly as the fault is cleared. A prolonged trip command may
Section 12
1MRK 506 375-UEN A
Control
234
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...