The default length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a
disconnector (SXSWI).
12.3.3.4
Proxy for signals from switching device via GOOSE XLNPROXY
GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1
The
SwitchType
setting controls the evaluation of the operating capability. If
SwitchType
is set to
Circuit Breaker
, the input OPCAP is interpreted as a breaker
operating capability, otherwise it is interpreted as a switch operating capability.
Table 28:
Operating capability values for breaker/switches
Value
Breaker operating capability, CbOpCap
Switch operating capability, SwOpCap
1
None
None
2
Open
Open
3
Close – Open
Close
4
Open – Close – Open
Close and Open
5
Close – Open – Close – Open
Larger values handled as 4, both Close and
Open
6
Open – Close – Open – Close – Open
7
more
tStartMove
is the supervision time for the apparatus to start moving after a
command execution is done from the SCSWI function. When the time has expired,
the command supervision is reset, and a cause-code is given.
During the
tIntermediate
time, the position indication is allowed to be in an
intermediate (00) state. When the time has expired, the command supervision is
reset, and a cause-code is given. The indication of the mid-position at SCSWI is
suppressed during this time period when the position changes from open to close or
vice-versa if the parameter
SuppressMidPos
is set to
On
in the SCSWI function.
In most cases, the same value can be used for both
tStartMove
and
tIntermediate
as
in the source function. However,
tStartMove
may need to be increased to
accommodate for the communication delays, mainly when representing a circuit
breaker.
12.3.3.5
Bay Reserve (QCRSV)
M16677-3 v3
The timer
tCancelRes
defines the supervision time for canceling the reservation,
when this cannot be done by requesting bay due to for example communication
failure.
When the parameter
ParamRequestx
(
x
=1-8) is set to
Only own bay res.
individually for each apparatus (x) in the bay, only the own bay is reserved, that is,
the output for reservation request of other bays (RES_BAYS) will not be activated
at selection of apparatus x.
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
253
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...