Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
BH_LINE
(WA1)A1
(WA2)B1
B2
A2
en04000503.vsd
BH_LINE
BH_LINE BH_LINE
IEC04000503 V1 EN-US
Figure 111:
Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic is the same as for the logic for the double-breaker
configuration.
Signal
S1DC_OP
All disconnectors on bus-section 1 are open.
S2DC_OP
All disconnectors on bus-section 2 are open.
VPS1_DC
The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC
The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB
No transmission error from breaker and a half (BH) that contains the above
information.
12.4.7
Interlocking for busbar earthing switch BB_ES
IP14164-1 v4
12.4.7.1
Application
M15015-3 v7
The interlocking for busbar earthing switch (BB_ES) function is used for one
busbar earthing switch on any busbar parts according to figure
QC
en04000504.vsd
IEC04000504 V1 EN-US
Figure 112:
Switchyard layout BB_ES
M15053-4 v4
The signals from other bays connected to the module BB_ES are described below.
12.4.7.2
Signals in single breaker arrangement
M15053-6 v5
The busbar earthing switch is only allowed to operate if all disconnectors of the
bus-section are open.
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
279
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...