Figure 120:
Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic are the same as for the logic for the double busbar
configuration described in section “Signals in single breaker arrangement”.
Signal
BB_DC_OP
All disconnectors on this part of the busbar are open.
VP_BB_DC
The switch status of all disconnectors on this part of the busbar is valid.
EXDU_BB
No transmission error from any bay that contains the above information.
12.4.8
Interlocking for double CB bay DB
IP14167-1 v2
12.4.8.1
Application
M13585-3 v10
The interlocking for a double busbar double circuit breaker bay including
DB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected to
a double busbar arrangement according to figure
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
285
Application manual