Total Block:
Prevents any tap changer operation independently of the control
mode (automatic as well as manual).
Setting parameters for blocking that can be set in TR1ATCC or TR8ATCC under
general settings in PST/local HMI are listed in table
.
Table 32:
Blocking settings
Setting
Values (Range)
Description
OCBk
(automatically
reset)
Alarm
Auto Block
Auto&Man Block
When any one of the three HV currents exceeds the
preset value
IBlock, TR1ATCC or TR8ATCC will be
temporarily totally blocked. The outputs IBLK and
TOTBLK or AUTOBLK will be activated depending on the
actual parameter setting.
OVPartBk
(automatically
reset)
Alarm
Auto&Man Block
If the busbar voltage U
B
(not the compensated load point
voltage UVL) exceeds
Umax (see figure
will be initiated or further URAISE commands will be
blocked. If permitted by setting in PST configuration, Fast
Step Down (FSD) of the tap changer will be initiated in
order to re-enter the voltage into the range
Umin < U
B
<
Umax. The FSD function is blocked when the lowest
voltage tap position is reached. The time delay for the
FSD function is separately set. The output UHIGH will be
activated as long as the voltage is above
Umax.
UVPartBk
(automatically
reset)
Alarm
Auto&Man Block
If the busbar voltage U
B
(not the compensated load point
voltage U
L
) is between
Ublock and Umin (see figure
an alarm will be initiated or further ULOWER commands
will be blocked. The output ULOW will be activated.
UVBk
(automatically
reset)
Alarm
Auto Block
Auto&Man Block
If the busbar voltage U
B
falls below
Ublock this blocking
condition is active. It is recommended to block automatic
control in this situation and allow manual control. This is
because the situation normally would correspond to a
disconnected transformer and then it should be allowed to
operate the tap changer before reconnecting the
transformer. The outputs UBLK and TOTBLK or
AUTOBLK will be activated depending on the actual
parameter setting.
Table continues on next page
Section 12
1MRK 506 375-UEN A
Control
312
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...