Settable time limits for warning and alarm are provided. The time limit for
overflow indication is fixed to 999999.9 seconds.
14.12.3
Setting guidelines
GUID-2911D624-87D5-4427-BB2F-E0D1072394FA v3
The settings
tAlarm
and
tWarning
are user settable limits defined in seconds. The
achievable resolution of the settings depends on the level of the values defined.
A resolution of 10 ms can be achieved when the settings are defined within the
range
1.00
second ≤
tAlarm
≤
99 999.99
seconds
1.00
second ≤
tWarning
≤
99 999.99
seconds.
If the values are above this range, the resolution becomes lower due to the 32 bit
float representation
99 999.99
seconds <
tAlarm
≤
999 999.0
seconds
99 999.99
seconds <
tWarning
≤
999 999.0
seconds
Note that
tAlarm
and
tWarning
are independent settings, that is,
there is no check if
tAlarm
>
tWarning
.
The limit for the overflow supervision is fixed at 999999.9 seconds.
14.13
Comparator for integer inputs - INTCOMP
14.13.1
Identification
GUID-5992B0F2-FC1B-4838-9BAB-2D2542BB264D v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparison of integer values
INTCOMP
Int<=>
14.13.2
Application
GUID-4C6D730D-BB1C-45F1-A719-1267234BF1B9 v1
The function gives the possibility to monitor the level of integer values in the
system relative to each other or to a fixed value. It is a basic arithmetic function
that can be used for monitoring, supervision, interlocking and other logics.
Section 14
1MRK 506 375-UEN A
Logic
374
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...