The setting parameters are:
LineLength1
Set with length of section 1 in km
RL1
Set with positive sequence resistance of section 1 per phase
XL1
Set with positive sequence reactance of section 1 per phase
REOverRL1
Set with ratio of RE by RL of section 1, this can be derived from positive and
zero sequences impedances as:
1
*
2
1
01
1
RL
RL
R
REOverRL
IECEQUATION15082 V1 EN-US
Where
R01 is zero sequence resistance of section 1 per phase.
XEOverXL1
Set with ratio of XE by XL of section 1, this can be derived from positive and zero
sequences impedances as:
1
*
2
1
01
1
XL
XL
X
XEOverXL
IECEQUATION15083 V1 EN-US
Where
X01 is zero sequence reactance of section 1 per phase.
The settings are set in the same way for line sections 2, 3 and so on.
15.10.3.1
Setting example
GUID-F3F5D7EC-1574-45F1-8D54-632D6E66D960 v2
Consider a 110kV/16.7Hz system with three transmission line sections (see Figure
Source A
1
2
3
RFLO
Source B
IEC15000299-1-en.vsdx
IEC15000299 V1 EN-US
Figure 167:
Single line diagram with three line sections
RWRFLO function should set for the
NrOfSections
. Since number of transmission
line sections is three, the
NrOfSections
should also be set to three (3). Table
provides the system line specifications for three transmission lines.
Section 15
1MRK 506 375-UEN A
Monitoring
408
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...