3-end differential protection with two communication links
Ldcm312
Ldcm312
Ldcm313
Ldcm312
IEC16000077 V1 EN-US
Figure 190:
Three-end differential protection with two communication links
If the LDCM is in 2Mbit mode, you can send the three local currents as well as the
three remote currents from the other links by configuring the transmitters in IED-B:
1. Ldcm312 transmitter sends the local currents and the three currents received
by Ldcm313.
2. Ldcm313 transmitter sends the three local currents and the three currents
received from Ldcm312.
As a result, six currents are received in IED-A and IED-C. These currents can be
connected to the protection function together with the local three currents.
In order to forward the logic signals (for example, inter-trip or inter-
block) between IED-A and IED-C, the setting
LinkForwarded
should be defined. In IED-B, it is set to
LDCM313
for Ldcm312
and to
LDCM312
for ldcm313.
This setup results in a master-master-master configuration, but without the benefit
of reverting to a slave-master-slave configuration in case of a communication link
interruption. In case of a communication link interruption, all three IEDs would be
blocked.
19.1.2.1
Communication hardware solutions
M12844-11 v5
The LDCM (Line Data Communication Module) has an optical connection such
that two IEDs can be connected over a direct fibre, as shown in figure
distance to be covered with this solution is up to typical 3km (SR), 80km (MR) and
110km (LR).
Section 19
1MRK 506 375-UEN A
Remote communication
454
Railway application RER670 2.2 IEC
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...