21.6.2
Application
GUID-D58ECA9A-9771-443D-BF84-8EF582A346BF v4
Global base values function (GBASVAL) is used to provide global values,
common for all applicable functions within the IED. One set of global values
consists of values for current, voltage and apparent power and it is possible to have
twelve different sets.
This is an advantage since all applicable functions in the IED use a single source of
base values. This facilitates consistency throughout the IED and also facilitates a
single point for updating values when necessary.
Each applicable function in the IED has a parameter,
GlobalBaseSel
, defining one
out of the twelve sets of GBASVAL functions.
21.6.3
Setting guidelines
GUID-E3F5D754-BD17-4729-895B-957A09C2AC75 v4
UBase
: Phase-to-phase voltage value to be used as a base value for applicable
functions throughout the IED.
IBase
: Phase current value to be used as a base value for applicable functions
throughout the IED.
SBase
: Standard apparent power value to be used as a base value for applicable
functions throughout the IED, typically
SBase
=
UBase
·
IBase
.
21.7
Signal matrix for binary inputs SMBI
SEMOD55793-1 v2
21.7.1
Application
M15310-3 v2
The Signal matrix for binary inputs function SMBI is used within the Application
Configuration tool in direct relation with the Signal Matrix tool. SMBI represents
the way binary inputs are brought in for one IED configuration.
21.7.2
Setting guidelines
M15312-3 v3
There are no setting parameters for the Signal matrix for binary inputs SMBI
available to the user in Parameter Setting tool. However, the user shall give a name
to SMBI instance and the SMBI inputs, directly in the Application Configuration
tool. These names will define SMBI function in the Signal Matrix tool. The user
defined name for the input or output signal will also appear on the respective
output or input signal.
1MRK 506 375-UEN A
Section 21
Basic IED functions
Railway application RER670 2.2 IEC
467
Application manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 48: ...42 ...
Page 70: ...64 ...
Page 80: ...74 ...
Page 100: ...94 ...
Page 210: ...204 ...
Page 364: ...358 ...
Page 384: ...378 ...
Page 468: ...462 ...
Page 494: ...488 ...
Page 504: ...498 ...
Page 505: ...499 ...