10.12.5.1
Completing the test
GUID-325F040B-BADC-4281-B965-9B7D6BFA3E15 v2
Continue to test another function or end the test by changing the Test mode setting
to
Off
. Restore connections and settings to their original values, if they were
changed for testing purposes.
10.12.6
Fault locator RWRFLO
GUID-345068D9-3CD0-41F5-BEEA-85D39DD5EDEF v1
Prepare the IED for verification of settings outlined in Section
.
10.12.6.1
Verifying signals and settings
GUID-D928E80E-F2DD-4704-9C6C-5AB4302A7D33 v2
The fault locator (RWRFLO) relies on information from two other functions:
•
Phase selection information provided by the distance protection function
•
Analog information provided by the trip value recorder function
Check that binary start and phase selection signals are connected, and that voltage
and current signals are configured (parameter settings).
The result is displayed on the local HMI or via PCM600. Distance-to-faults for the
last 1000 recorded disturbances can be found on the local HMI under
Main menu/
Disturbance records/Disturbance #n (n = 1-100)/General Information
.
In PCM600, including loop selection information the result is displayed on the
recording list after upload.
The function can be selected for
2Phase
or
ATCatenary
using the setting
SystemType
. Sequence of voltage and current to be applied for verifying signals and
settings.
1MRK 506 377-UEN C
Section 10
Testing functionality by secondary injection
Railway application RER670 2.2 IEC
169
Commissioning manual
Summary of Contents for RELION RER670
Page 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Commissioning manual...
Page 2: ......
Page 26: ...20...
Page 54: ...48...
Page 58: ...52...
Page 62: ...56...
Page 80: ...74...
Page 188: ...182...
Page 194: ...188...
Page 204: ...198...
Page 214: ...208...
Page 215: ...209...