IEC15000025 V1 EN-US
5.
Select and edit the values.
6.
Click
Acknowledge and send
.
IEC15000026 V1 EN-US
This commits the values to the IED and exits the editing session.
7.
Click
Cancel
to abort the changes and revert back to actual IED values.
IEC15000032 V1 EN-US
Regardless if the forcing changes are commited or canceled, the
forcing is still active.
To force more signals, click the button
Start editing signal value for forcing
again.
9.8.4
How to undo forcing changes and return the IED to normal
operation
GUID-00E2BAD8-A29E-4B9D-80E6-E12F59E019BD v1
Regardless of which input/output signals have been forced, all forced signals will
return to their normal states immediately when the IED is taken out of test mode.
1MRK 506 377-UEN C
Section 9
Testing IED operation
Railway application RER670 2.2 IEC
71
Commissioning manual