IEC15000430-2-en.vsdx
RLd
R
jX
P1
P2
P3
P4
P5
P6
P7
P8
Z1CircleStart
RLd
LineAng
ArgLd
( )
( )
IEC15000430 V2 EN-US
Figure 14:
Proposed test points for phase-to-phase loop of circular
characteristic in solidly earthed system
Table 16:
Test points for phase-to-phase loop of circular characteristic
Test point
R
X
Comment
P1
Z1CircleStart ∗
cos(
LineAng)
Z1CircleStart ∗
sin(
LineAng)
P2
0.8 ∗
Z1CircleStart ∗
cos(
ArgLd)
0.8 ∗
Z1CircleStart ∗
sin(
ArgLd)
P3
RLd
0
P4
-
Z1CircleStart ∗
cos(
LineAng)
-
Z1CircleStart ∗
sin(
LineAng)
P5
-0.8 ∗
Z1CircleStart ∗
cos(
ArgLd)
-0.8 ∗
Z1CircleStart ∗
sin(
ArgLd)
P6
-RLd
0
P7
Z1CircleStart ∗
cos(
ArgLd)
-
Z1CircleStart ∗
sin(
ArgLd)
P8
-
Z1CircleStart ∗
cos(
ArgLd)
Z1CircleStart ∗
sin(
ArgLd)
1MRK 506 377-UEN C
Section 10
Testing functionality by secondary injection
Railway application RER670 2.2 IEC
85
Commissioning manual