11.1.2.2
Base quantities for CVGAPC function
SEMOD53443-112 v4
The parameter settings for the base quantities, which represent the base (100%) for
pickup levels of all measuring stages shall be entered as setting parameters for
every CVGAPC function.
Base current shall be entered as:
1. rated phase current of the protected object in primary amperes, when the
measured Current Quantity is selected from 1 to 9, as shown in table
.
2. rated phase current of the protected object in primary amperes multiplied by
√3 (1.732 x Iphase), when the measured Current Quantity is selected from 10
to 15, as shown in table
Base voltage shall be entered as:
1. rated phase-to-earth voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 1 to 9, as shown in table
2. rated phase-to-phase voltage of the protected object in primary kV, when the
measured Voltage Quantity is selected from 10 to 15, as shown in table
.
11.1.2.3
Application possibilities
SEMOD53443-136 v3
Due to its flexibility the general current and voltage protection (CVGAPC)
function can be used, with appropriate settings and configuration in many different
applications. Some of possible examples are given below:
1. Transformer and line applications:
•
Underimpedance protection (circular, non-directional characteristic)
•
Underimpedance protection (circular mho characteristic)
•
Voltage Controlled/Restrained Overcurrent protection
•
Phase or Negative/Positive/Zero Sequence (Non-Directional or
Directional) Overcurrent protection
•
Phase or phase-to-phase or Negative/Positive/Zero Sequence over/under
voltage protection
•
Thermal overload protection
•
Open Phase protection
•
Unbalance protection
2. Generator protection
•
80-95% Stator earth fault protection (measured or calculated 3Uo)
•
Rotor earth fault protection (with external COMBIFLEX RXTTE4
injection unit)
•
Underimpedance protection
•
Voltage Controlled/Restrained Overcurrent protection
•
Turn-to-Turn & Differential Backup protection (directional Negative
Sequence. Overcurrent protection connected to generator HV terminal
CTs looking into generator)
•
Stator Overload protection
1MRK 511 407-UEN C
Section 11
Multipurpose protection
Phasor measurement unit RES670 2.2 IEC
193
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...