Example for use of GRP_OFF signal in FXDSIGN
The Restricted earth fault function (REFPDIF) can be used both for auto-
transformers and normal transformers.
When used for auto-transformers, information from both windings parts, together
with the neutral point current, needs to be available to the function. This means that
three inputs are needed.
I3PW1CT1
I3PW2CT1
I3P
REFPDIF
IEC09000619_3_en.vsd
IEC09000619 V3 EN-US
Figure 84:
REFPDIF function inputs for autotransformer application
For normal transformers only one winding and the neutral point is available. This
means that only two inputs are used. Since all group connections are mandatory to
be connected, the third input needs to be connected to something, which is the
GRP_OFF signal in FXDSIGN function block.
I3PW1CT1
I3PW2CT1
I3P
REFPDIF
GRP_OFF
FXDSIGN
IEC09000620_3_en.vsd
IEC09000620 V3 EN-US
Figure 85:
REFPDIF function inputs for normal transformer application
15.8
Boolean 16 to Integer conversion B16I
SEMOD175715-1 v1
15.8.1
Identification
SEMOD175721-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion
B16I
-
-
Section 15
1MRK 511 407-UEN C
Logic
238
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...