The high and low limit settings provides limits for the high-high-, high, normal,
low and low-low ranges of the measured value. The actual range of the measured
value is shown on the range output of MVGAPC function block. When a Measured
value expander block (RANGE_XP) is connected to the range output, the logical
outputs of the RANGE_XP are changed accordingly.
19.2.3.2
Receiving data
GUID-CAE4B020-7131-49BF-BA29-3EEE0EFEA2B8 v2
The GOOSE data must be received at function blocks. There are different GOOSE
receiving function blocks depending on the type of the received data. Refer to the
Engineering manual for more information about how to configure GOOSE.
Function block type
Data Type
GOOSEBINRCV
16 single point
GOOSEINTLKRCV
2 single points
16 double points
GOOSEDPRCV
Double point
GOOSEINTRCV
Integer
GOOSEMVRCV
Analog value
GOOSESPRCV
Single point
GOOSEXLNRCV
Switch status
Application
GUID-808177B7-02CA-40DF-B41B-8B580E38478B v1
The GOOSE receive function blocks are used to receive subscribed data from the
GOOSE protocol. The validity of the data value is exposed as outputs of the
function block as well as the validity of the communication. It is recommended to
use these outputs to ensure that only valid data is handled on the subscriber IED.
An example could be to control the external reservation before operating on a bay.
In the figure below, the GOOSESPRCV is used to receive the status of the bay
reservation. The validity of the received data is used in additional logic to
guarantee that the value has good quality before operation on that bay.
GOOSESPRCV
Block Spout
DataValid
CommValid
Test
AND
AND
Input1 out
Input2 Noput
Input3
Input4
Input1 out
Input2 Noput
Input3
Input4
Ext_Res_OK_To_Operate
IEC16000082=1=en.vsd
IEC16000082 V1 EN-US
Figure 100:
GOOSESPRCV and AND function blocks - checking the validity of
the received data
Section 19
1MRK 511 407-UEN C
Station communication
294
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...