en06000519-2.vsd
IEC06000519 V2 EN-US
Figure 115:
Direct fiber optical connection between two IEDs with LDCM
The LDCM can also be used together with an external optical to galvanic G.703
converter as shown in figure
. These solutions are aimed for connections to a
multiplexer, which in turn is connected to a telecommunications transmission
network (for example PDH).
Telecom. Network
*)
*)
Multiplexer
Multiplexer
en05000527-2.vsd
*) Converting optical to galvanic G.703
IEC05000527 V2 EN-US
Figure 116:
LDCM with an external optical to galvanic converter and a
multiplexer
When an external modem G.703 is used, the connection between LDCM and the
modem is made with a multimode fiber of max. 3 km length. The IEEE/ANSI
C37.94 protocol is always used between LDCM and the modem.
20.1.3
Setting guidelines
M12454-3 v7
64 kbit and 2 Mbit mode common settings
ChannelMode
defines how an IED discards the LDCM information when one of
the IEDs in the system is out of service: it can either be done on the IED out of
service by setting all local LDCMs to channel mode
OutOfService
or at the remote
end by setting the corresponding LDCM to channel mode
Blocked
. If
OutOfService
1MRK 511 407-UEN C
Section 20
Remote communication
Phasor measurement unit RES670 2.2 IEC
325
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...