Transformer and
Line protection
Transformer
Line
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Forward
Reverse
Definition of direction
for directional
line functions
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Setting of current input
for line functions:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IED
IEC05000462 V2 EN-US
Figure 9:
Example how to set CTStarPoint parameters in the IED