Name
Type
Values (Range)
Unit
Description
FREQREFCHSEL
INTEGER
-
-
Frequency reference
channel number
selected
FREQREFCHERR
BOOLEAN
0=Freq ref not
available
1=Freq ref error
2=Freq ref
available
-
Frequency reference
channel error
FREQTRIG
BOOLEAN
-
-
Frequency trigger
DFDTTRIG
BOOLEAN
-
-
Rate of change of
frequency trigger
MAGHIGHTRIG
BOOLEAN
-
-
Magnitude high trigger
MAGLOWTRIG
BOOLEAN
-
-
Magnitude low trigger
6.1.3.2
Reporting filters
GUID-D39153B5-81CE-4C1F-A816-C7A4C3407048 v2
The PMUREPORT function block implements the reporting filters designed to
avoid aliasing as the reporting frequency is lower than the sample/calculation
frequency. This means, the synchrophasor and frequency data which are included
in the C37.118 synchrophasor streaming data are filtered in order to suppress
aliasing effects, as the rate of the C37.118 data is slower than the data rate for
internal processing. For this purpose, there is an anti-aliasing filter designed for
each reporting rate. The correct anti-aliasing filter will be automatically selected
based on the reporting rate and the performance class (P/M) settings. The filters are
designed to attenuate all aliasing frequencies to at least -40 dB (a gain of 0.01) at
M class.
The synchrophasor measurement is adaptive as it follows the
fundamental frequency over a wide range despite the reporting rate.
For example, when the synchrophasor measurement follows the fundamental
frequency beyond the fixed Nyquist limits in C37.118 standard, the anti-aliasing
filter stopband moves with the measured fundamental frequency. This has to be
considered in connection with C37.118, where the passband is defined relative to a
fixed nominal frequency as shown in the equation
.
0
2
s
F
f
±
IECEQUATION2418 V1 EN-US
(Equation 12)
where,
f
0
is the nominal frequency
F
s
is the reporting rate
1MRK 511 407-UEN C
Section 6
Wide area measurement system
Phasor measurement unit RES670 2.2 IEC
93
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...