Name
Values (Range)
Unit
Step
Default
Description
tCCrv2
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 2
tPRCrv2
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset time
curve for step 2
tTRCrv2
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset time
curve for step 2
tCRCrv2
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse reset time
curve for step 2
ResetTypeCrv3
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step3 (Instantaneous /
IEC / ANSI)
tReset3
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 3
tPCrv3
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time
curve for step 3
tACrv3
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time
curve for step 3
tBCrv3
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time
curve for step 3
tCCrv3
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 3
tPRCrv3
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset time
curve for step 3
tTRCrv3
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset time
curve for step 3
tCRCrv3
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset time
curve for step 3
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step4 (Instantaneous /
IEC / ANSI)
tReset4
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 4
tPCrv4
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time
curve for step 4
tACrv4
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time
curve for step 4
tBCrv4
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time
curve for step 4
tCCrv4
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time
curve for step 4
tPRCrv4
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset time
curve for step 4
tTRCrv4
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset time
curve for step 4
tCRCrv4
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset time
curve for step 4
Section 8
1MRK 511 408-UUS A
Current protection
220
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...