8.5.3
Function block
M12627-3 v8
LCPTTR (26)
I3P*
BLOCK
BLKTR
MULTPU
AMBTEMP
SENSFLT
RESET
TRIP
BFI_3P
ALARM
LOCKOUT
ANSI14000052-1-en.vsd
ANSI13000199 V2 EN-US
LFPTTR (26)
I3P*
BLOCK
BLKTR
MULTPU
AMBTEMP
SENSFLT
RESET
TRIP
BFI_3P
ALARM
LOCKOUT
ANSI14000054-1-en.vsd
ANSI13000301 V2 EN-US
Figure 77:
LFPTTR/LCPTTR (26) function block
8.5.4
Signals
PID-3908-INPUTSIGNALS v7
Table 121:
LCPTTR (26) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current input
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Block of trip
MULTPU
BOOLEAN
0
Current multiplyer used when THOL is for two or more
lines
AMBTEMP
REAL
0
Ambient temperature from external temperature
sensor
SENSFLT
BOOLEAN
0
Validity status of ambient temperature sensor
RESET
BOOLEAN
0
Reset of internal thermal load counter
PID-3909-INPUTSIGNALS v9
Table 122:
LFPTTR (26) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current input
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Block of trip
Table continues on next page
Section 8
1MRK 511 408-UUS A
Current protection
244
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...