8.6.5
Settings
PID-3709-SETTINGS v6
Table 134:
GUPPDUP (37) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
OpMode1
Disabled
UnderPower
-
-
UnderPower
Operation mode for stage 1 Off / On
Power1
0.0 - 500.0
%SB
0.1
1.0
Stage 1 underpower setting in Angle1
direction in % of SBase
Angle1
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for max power senistivity
stage 1
TripDelay1
0.01 - 6000.00
s
0.01
1.00
Trip delay for stage 1
DropDelay1
0.01 - 6000.00
s
0.01
0.06
Drop-off delay for stage 1
OpMode2
Disabled
UnderPower
-
-
UnderPower
Operation mode for stage 2 Off / On
Power2
0.0 - 500.0
%SB
0.1
1.0
Power setting for stage 2 in % of SBase
Angle2
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for max power senistivity
stage 2
TripDelay2
0.01 - 6000.00
s
0.01
1.00
Trip delay for stage 2
DropDelay2
0.01 - 6000.00
s
0.01
0.06
Drop-off delay for stage 2
Table 135:
GUPPDUP (37) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
TD
0.000 - 0.999
-
0.001
0.000
Low pass filter coefficient for power
measurement, P and Q
Hysteresis1
0.2 - 5.0
%SB
0.1
0.5
Absolute hysteresis of stage 1 in % SBase
Hysteresis2
0.2 - 5.0
%SB
0.1
0.5
Absolute hysteresis of stage 2 in % SBase
IMagComp5
-10.000 - 10.000
%
0.001
0.000
Amplitude correction compensates current
error at 5% of Ir
IMagComp30
-10.000 - 10.000
%
0.001
0.000
Amplitude correction compensates current
error at 30% of Ir
IMagComp100
-10.000 - 10.000
%
0.001
0.000
Amplitude correction compensates current
error at 100% of Ir
VMagComp5
-10.000 - 10.000
%
0.001
0.000
Amplitude correction compensates voltage
error at 5% of Ur
VMagComp30
-10.000 - 10.000
%
0.001
0.000
Amplitude correction compensates voltage
error at 30% of Ur
VMagComp100
-10.000 - 10.000
%
0.001
0.000
Amplitude correction compensates voltage
error at 100% of Ur
Table continues on next page
Section 8
1MRK 511 408-UUS A
Current protection
254
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...