8.7.8
Technical data
SEMOD175160-1 v1
SEMOD175159-2 v9
Table 147:
GOPPDOP (32) technical data
Function
Range or value
Accuracy
Power level
for Step 1 and Step 2
(0.0–500.0)% of SBase
±1.0% of S
n
at S ≤ S
n
±1.0% of S at S > S
n
Characteristic angle
for Step 1 and Step 2
(-180.0–180.0) degrees
±2.0 degrees
Trip time, pickup at 0.5 x S
r
to 2 x S
r
and
k=0.000
Min. =10 ms
Max. = 25 ms
Reset time, pickup at 2 x S
r
to 0.5 x S
r
and
k=0.000
Min. = 35 ms
Max. = 55 ms
Independent time delay to trip for Step 1 and
Step 2 at 0.5 x S
n
to 2 x S
n
and
k=0.000
(0.01-6000.00) s
±0.2% or ±40 ms
whichever is greater