ANSI05000170 V1 EN-US
Figure 120:
CVGAPC function main logic diagram for built-in protection elements
can be summarized as follows:
1. The selected currents and voltage are given to built-in protection elements. Each
protection element and step makes independent decision about status of its
PICKUP and TRIP output signals.
2. More detailed internal logic for every protection element is given in the following
four figures.
3. Common PICKUP and TRIP signals from all built-in protection elements & steps
(internal OR logic) are available from multipurpose function as well.
Second
harmonic check
Selected voltage
X
PickupCurr_OC1
a
b
a>b
Voltage
control or
restraint
feature
OC1=On
BLKOC1
Directionality
check
Current
Restraint
Feature
I
measured
> k I
restraint
DIR_OK
Inverse
0-DEF
DEF time
selected
Inverse
time
selected
OR
Enable
second
harmonic
en05000831_ansi.vsd
Selected current
PU_OC1
TROC1
AND
BLKTROC1
Selected restrain current
AND
NOT
0
ANSI05000831 V1 EN-US
Figure 121:
Simplified internal logic diagram for built-in first overcurrent step that is, OC1 (step OC2 has the
same internal logic)
1MRK 511 408-UUS A
Section 11
Multipurpose protection
Phasor measurement unit RES670 2.2 ANSI
349
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...