breaker(s) the pulse time shall be set to at least 0.150 seconds in order to obtain
satisfactory minimum duration of the trip pulse to the circuit breaker trip coils.
15.3.7
Technical data
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
Table 241:
Number of TMAGAPC instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
TMAGAPC
6
6
-
15.4
Logic for group alarm ALMCALH
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
15.4.1
Identification
GUID-64EA392C-950F-486C-8D96-6E7736B592BF v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logic for group alarm
ALMCALH
-
-
15.4.2
Functionality
GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v4
The group alarm logic function (ALMCALH) is used to route several alarm signals to a
common indication, LED and/or contact, in the IED.
15.4.3
Function block
GUID-EA192656-71DD-4D44-A1D5-96B1B4937971 v1
ALMCALH
BLOCK
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
INPUT9
INPUT10
INPUT11
INPUT12
INPUT13
INPUT14
INPUT15
INPUT16
ALARM
IEC13000181-1-en.vsd
IEC13000181 V1 EN-US
1MRK 511 408-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.2 ANSI
423
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...