15.6.6
Operation principle
GUID-72B1B4E8-BC6C-4AF7-8B41-058241B944F8 v2
The logic for group indication INDCALH block is provided with 16 input signals and
1 IND output signal. The function block incorporates internal logic OR gate in order to
provide grouping of connected input signals to the output IND signal from the function
block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the IND
output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a
steady signal.
IND
1
ANSI13000193-1-en.vsd
INPUT1
INPUT16
200 ms
0
ANSI13000193 V1 EN-US
15.6.7
Technical data
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v1
Table 253:
Number of INDCALH instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
INDCALH
-
5
-
15.7
Basic configurable logic blocks
M11396-4 v16
The basic configurable logic blocks do not propagate the time stamp and quality of
signals (have no suffix QT at the end of their function name). A number of logic blocks
and timers are always available as basic for the user to adapt the configuration to the
specific application needs. The list below shows a summary of the function blocks and
their features.
These logic blocks are also available as part of an extension logic package with the
same number of instances.
Section 15
1MRK 511 408-UUS A
Logic
430
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...