15.7.2
Controllable gate function block GATE
IP11021-1 v2
M11489-3 v2
The Controllable gate function block (GATE) is used for controlling if a signal should
be able to pass from the input to the output or not depending on a setting.
15.7.2.1
Function block
M11490-3 v2
IEC04000410-2-en.vsd
GATE
INPUT
OUT
IEC04000410 V2 EN-US
Figure 159:
GATE function block
15.7.2.2
Signals
PID-3801-INPUTSIGNALS v6
Table 257:
GATE Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input to gate
PID-3801-OUTPUTSIGNALS v5
Table 258:
GATE Output signals
Name
Type
Description
OUT
BOOLEAN
Output from gate
15.7.2.3
Settings
PID-3801-SETTINGS v6
Table 259:
GATE Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
15.7.2.4
Technical data
GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v2
Table 260:
Number of GATE instances
Logic block
Quantity with cycle time
3 ms
8 ms
100 ms
GATE
10
10
20