Name
Type
Default
Description
IN12
BOOLEAN
0
Input 12
IN13
BOOLEAN
0
Input 13
IN14
BOOLEAN
0
Input 14
IN15
BOOLEAN
0
Input 15
IN16
BOOLEAN
0
Input 16
PID-6944-OUTPUTSIGNALS v2
Table 339:
BTIGAPC Output signals
Name
Type
Description
OUT
INTEGER
Output value
15.12.5
Settings
ABBD8E283673 v3
The function does not have any parameters available in the local HMI or PCM600.
15.12.6
Monitored data
PID-6944-MONITOREDDATA v2
Table 340:
BTIGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
OUT
INTEGER
-
-
Output value
15.12.7
Operation principle
SEMOD158425-4 v6
The Boolean 16 to integer conversion with logic node representation function
(BTIGAPC) will transfer a combination of up to 16 binary inputs INx, where 1≤x≤16,
to an integer. Each INx represents a value according to the table below from 0 to
32768. This follows the general formula: INx = 2
x-1
where 1≤x≤16. The sum of all the
values on the activated INx will be available on the output OUT as a sum of the integer
values of all the inputs INx that are activated. OUT is an integer. When all INx (where
1≤x≤16) are activated, that is = Boolean 1, it corresponds to that integer 65535 is
available on the output OUT. If the BLOCK input is activated, it will freeze the logical
outputs at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output
OUT on the function block BTIGAPC.
1MRK 511 408-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.2 ANSI
467
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...