Name
Values (Range)
Unit
Step
Default
Description
InitAccCurrPwr
0.00 - 9999.99
-
0.01
0.00
Initial value for accum I^CurrExponent integr
over CB open travel time value
InitInactDays
0 - 9999
Day
1
0
Initial value for inactive days
InactiveAlHrs
0 - 23
Hour
1
0
Alarm time for inactive days counter in hours
16.4.6
Monitored data
PID-3267-MONITOREDDATA v7
Table 413:
SSCBR Monitored data
Name
Type
Values (Range)
Unit
Description
TTRVOP
REAL
-
ms
Travel time of the CB during
opening operation
TTRVCL
REAL
-
ms
Travel time of the CB during
closing operation
NOOPER
INTEGER
-
-
Number of CB operation
cycle
CBLIFEPH
INTEGER
-
-
CB Remaining life of
respective phase
INADAYS
INTEGER
-
-
The number of days CB has
been inactive
IPOWPH
REAL
-
-
Accumulated I^CurrExponent
integrated over CB open
travel time
SPCHT
REAL
-
s
The charging time of the CB
spring
16.4.7
Operation principle
GUID-3902D69C-1858-40DD-AD63-C33C381697BA v12
The breaker monitoring function includes metering and monitoring subfunctions. The
subfunctions can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are
Enabled
and
Disabled
.
The operation of the subfunctions is described by the module diagram as shown in
figure
. All the modules in the diagram are explained in subsequent sections.
Section 16
1MRK 511 408-UUS A
Monitoring
536
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...