Function
Range or value
Accuracy
Maximum number of binary inputs
352
-
Maximum number of phasors in the Trip
Value recorder per recording
30
-
Maximum number of indications in a
disturbance report
352
-
Maximum number of events in the Event
recording per recording
150
-
Maximum number of events in the
Sequence of events
1000, first in - first out
-
Maximum total recording time (3.4 s
recording time and maximum number of
channels, typical value)
340 seconds (100 recordings)
at 50 Hz, 280 seconds (80
recordings) at 60 Hz
-
Sampling rate
1 kHz at 50 Hz
1.2 kHz at 60 Hz
-
Recording bandwidth
(5-300) Hz
-
16.7
Logical signal status report BINSTATREP
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
16.7.1
Identification
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Logical signal status report
BINSTATREP
-
-
16.7.2
Functionality
GUID-A72E490D-01F7-4874-B010-8BDE38391D88 v3
The Logical signal status report (BINSTATREP) function makes it possible for a SPA
master to poll signals from various other functions.
Section 16
1MRK 511 408-UUS A
Monitoring
580
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...