16.10.4
Signals
PID-6998-INPUTSIGNALS v1
Table 439:
TEILGAPC Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Freeze the accumulation and block the outputs
IN
BOOLEAN
0
The input signal that is used to measure the elapsed
time, when its value is high
ADDTIME
BOOLEAN
0
Add time to the accumulation
RESET
BOOLEAN
0
Reset accumulated time
PID-6998-OUTPUTSIGNALS v1
Table 440:
TEILGAPC Output signals
Name
Type
Description
ALARM
BOOLEAN
Indicator that accumulated time has reached alarm
limit
WARNING
BOOLEAN
Indicator that accumulated time has reached warning
limit
OVERFLOW
BOOLEAN
Indicator that accumulated time has reached overflow
limit
ACC_HOUR
REAL
Accumulated time in hours
ACC_DAY
REAL
Accumulated time in days
16.10.5
Settings
PID-6998-SETTINGS v1
Table 441:
TEILGAPC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
tAlarm
1.0 - 99999.9
Hour
0.1
90000.0
Time limit for alarm supervision
tWarning
1.0 - 99999.9
Hour
0.1
50000.0
Time limit for warning supervision
tAddToTime
0.0 - 99999.9
Hour
0.1
0.0
Time to add to the accumulation
16.10.6
Operation principle
GUID-C7F91D4E-5942-4006-B7C8-4F499E7DC49D v3
Figure
describes the simplified logic of the function.
1MRK 511 408-UUS A
Section 16
Monitoring
Phasor measurement unit RES670 2.2 ANSI
591
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...