19.7.3.3
Function block
GUID-C234101E-F9B9-4DB0-874C-C51BB50588CB v1
IEC10000288-1-en.vsd
I103MEASUSR
BLOCK
^INPUT1
^INPUT2
^INPUT3
^INPUT4
^INPUT5
^INPUT6
^INPUT7
^INPUT8
^INPUT9
IEC10000288 V1 EN-US
Figure 269:
I103MEASUSR function block
19.7.3.4
Signals
PID-3791-INPUTSIGNALS v5
Table 507:
I103MEASUSR Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of service value reporting
INPUT1
REAL
0.0
Service value for measurement on input 1
INPUT2
REAL
0.0
Service value for measurement on input 2
INPUT3
REAL
0.0
Service value for measurement on input 3
INPUT4
REAL
0.0
Service value for measurement on input 4
INPUT5
REAL
0.0
Service value for measurement on input 5
INPUT6
REAL
0.0
Service value for measurement on input 6
INPUT7
REAL
0.0
Service value for measurement on input 7
INPUT8
REAL
0.0
Service value for measurement on input 8
INPUT9
REAL
0.0
Service value for measurement on input 9
19.7.3.5
Settings
PID-3791-SETTINGS v5
Table 508:
I103MEASUSR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
25
Function type (1-255)
InfNo
1 - 255
-
1
1
Information number for measurands (1-255)
MaxMeasur1
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on input 1
MaxMeasur2
0.05 -
10000000000.00
-
0.05
1000.00
Maximum value for measurement on input 2
Table continues on next page
Section 19
1MRK 511 408-UUS A
Station communication
688
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...