19.7.15.4
Signals
PID-6578-INPUTSIGNALS v5
Table 535:
I103POSCMDV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
POSITION
INTEGER
0
Position of controllable object
19.7.15.5
Settings
PID-6578-SETTINGS v6
Table 536:
I103POSCMDV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type
InfNo
160 - 209
-
1
160
Information number for command output
19.7.16
Operation principle
IP14407-1 v3
19.7.16.1
General
M11874-3 v5
IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system, and with a data transfer
rate up to 38400 bit/s. In IEC terminology, a primary station is a master and a
secondary station is a slave. The communication is based on a point-to-point principle.
The master must have software that can interpret IEC 60870-5-103 communication
messages.
Introduction to IEC 60870–5–103 protocol
M11874-6 v3
IEC 60870-5-103 protocol functionality consists of the following functions:
•
Event handling
•
Report of analog service values (measurements)
•
Fault location
•
Command handling
Section 19
1MRK 511 408-UUS A
Station communication
708
Phasor measurement unit RES670 2.2 ANSI
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...