22.11.2
Functionality
GUID-D58ECA9A-9771-443D-BF84-8EF582A346BF v4
Global base values function (GBASVAL) is used to provide global values, common for
all applicable functions within the IED. One set of global values consists of values for
current, voltage and apparent power and it is possible to have twelve different sets.
This is an advantage since all applicable functions in the IED use a single source of
base values. This facilitates consistency throughout the IED and also facilitates a single
point for updating values when necessary.
Each applicable function in the IED has a parameter,
GlobalBaseSel
, defining one out
of the twelve sets of GBASVAL functions.
22.11.3
Settings
GUID-C73A66FB-5D6E-4DC3-B8B5-046AEC2F1FDE v1
PID-4026-SETTINGS v7
Table 621:
GBASVAL Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
VBase
0.05 - 2000.00
kV
0.05
400.00
Global base voltage
IBase
1 - 99999
A
1
3000
Global base current
SBase
1.00 - 200000.00
MVA
0.05
2000.00
Global base apparent power
22.12
Primary system values PRIMVAL
22.12.1
Identification
GUID-B8B3535D-227B-4151-9E98-BEB85F4D54DE v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Primary system values
PRIMVAL
-
-
22.12.2
Functionality
M15288-3 v6
The rated system frequency and phase rotation direction are set under
Main menu/
Configuration/ Power system/ Primary Values
in the local HMI and PCM600
parameter setting tree.
1MRK 511 408-UUS A
Section 22
Basic IED functions
Phasor measurement unit RES670 2.2 ANSI
795
Technical manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 ANSI Technical manual ...
Page 2: ......
Page 276: ...270 ...
Page 306: ...300 ...
Page 360: ...354 ...
Page 406: ...400 ...
Page 614: ...608 ...
Page 732: ...726 ...
Page 748: ...742 ...
Page 884: ...878 ...
Page 932: ...926 ...
Page 933: ...927 ...