ANSI08000479 V1 EN-US
Figure 309:
TRM connection diagram
23.2.5.3
Technical data
SEMOD55412-1 v1
M16988-1 v11
Table 634:
TRM - Energizing quantities, rated values and limits for protection transformer
Description
Value
Frequency
Rated frequency f
r
50/60 Hz
Operating range
f
r
± 10%
Current inputs
Rated current I
r
1 or 5 A
Operating range
(0-100) x I
r
Thermal withstand
100 × I
r
for 1 s *)
30 × I
r
for 10 s
10 × I
r
for 1 min
4 × I
r
continuously
Table continues on next page
1MRK 511 408-UUS A
Section 23
IED hardware
Phasor measurement unit RES670 2.2 ANSI
809
Technical manual