Figure 46:
Protected power line as part of a two-machine system
Reduce the power system with protected power line into an equivalent two-
machine system with positive sequence source impedances Z
SA
behind the
protective relay R and Z
SB
behind the remote end bus B. Observe the fact that these
impedances cannot be directly calculated from the maximum three-phase short
circuit currents for faults on the corresponding busbar. It is necessary to consider
separate contributions of different connected circuits.
The required data is as follows:
400
r
U
kV
=
EQUATION1321 V1 EN-US
Rated system voltage
min
380
U
kV
=
EQUATION1322 V1 EN-US
Minimum expected system voltage under critical system
conditions
50
r
f
Hz
=
EQUATION1323 V1 EN-US
Rated system frequency
400
3
p
U
kV
=
EQUATION1324 V1 EN-US
Rated primary voltage of voltage (or potential) transformers
used
0.11
3
s
U
kV
=
EQUATION1325 V1 EN-US
Rated secondary voltage of voltage (or potential) transformers
used
1200
p
I
A
=
EQUATION1326 V1 EN-US
Rated primary current of current transformers used
1
s
I
A
=
EQUATION1327 V1 EN-US
Rated secondary current of current transformers used
(
)
1
10.71
75.6
L
Z
j
=
+
W
EQUATION1328 V1 EN-US
Positive sequence line impedance
(
)
1
1.15
43.5
SA
Z
j
=
+
W
EQUATION1329 V1 EN-US
Positive sequence source impedance behind A bus
Table continues on next page
1MRK 511 407-UEN C
Section 7
Impedance protection
Phasor measurement unit RES670 2.2 IEC
109
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...