14.5.2
Application
SEMOD158637-5 v4
Automation bits, command function for DNP3 (AUTOBITS) is used within
PCM600 in order to get into the configuration the commands coming through the
DNP3.0 protocol.The AUTOBITS function plays the same role as functions
GOOSEBINRCV (for IEC 61850) and MULTICMDRCV (for LON).AUTOBITS
function block have 32 individual outputs which each can be mapped as a Binary
Output point in DNP3. The output is operated by a "Object 12" in DNP3. This
object contains parameters for control-code, count, on-time and off-time. To
operate an AUTOBITS output point, send a control-code of latch-On, latch-Off,
pulse-On, pulse-Off, Trip or Close. The remaining parameters are regarded as
appropriate. For example, pulse-On, on-time=100, off-time=300, count=5 would
give 5 positive 100 ms pulses, 300 ms apart.
For description of the DNP3 protocol implementation, refer to the Communication
manual.
14.5.3
Setting guidelines
SEMOD158639-5 v3
AUTOBITS function block has one setting, (
Operation
:
On
/
Off
) enabling or
disabling the function. These names will be seen in the DNP3 communication
management tool in PCM600.
14.6
Single command, 16 signals SINGLECMD
SEMOD119849-1 v2
14.6.1
Identification
GUID-2217CCC2-5581-407F-A4BC-266CD6808984 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single command, 16 signals
SINGLECMD
-
-
14.6.2
Application
M12445-3 v3
Single command, 16 signals (SINGLECMD) is a common function and always
included in the IED.
The IEDs may be provided with a function to receive commands either from a
substation automation system or from the local HMI. That receiving function block
has outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used. Together
with the configuration logic circuits, the user can govern pulses or steady output
signals for control purposes within the IED or via binary outputs.
Section 14
1MRK 511 407-UEN C
Control
222
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...