Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN11
BOOLEAN
0
Input 11
1024
0
IN12
BOOLEAN
0
Input 12
2048
0
IN13
BOOLEAN
0
Input 13
4096
0
IN14
BOOLEAN
0
Input 14
8192
0
IN15
BOOLEAN
0
Input 15
16384
0
IN16
BOOLEAN
0
Input 16
32768
0
The sum of the numbers in column “Value when activated” when all INx (where
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can
be converted to an integer by the BTIGAPC function block.
15.10
Integer to Boolean 16 conversion IB16
SEMOD158367-1 v2
15.10.1
Identification
SEMOD167941-2 v2
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion
IB16
-
-
15.10.2
Application
SEMOD158499-5 v4
Integer to boolean 16 conversion function (IB16) is used to transform an integer
into a set of 16 binary (logical) signals. It can be used – for example, to connect
integer output signals from one function to binary (logical) inputs to another
function. IB16 function does not have a logical node mapping.
The Boolean 16 to integer conversion function (IB16) will transfer a combination
of up to 16 binary inputs INx where 1≤x≤16 to an integer. Each INx represents a
value according to the table below from 0 to 32768. This follows the general
formula: INx = 2
x-1
where 1≤x≤16. The sum of all the values on the activated INx
will be available on the output OUT as a sum of the values of all the inputs INx
that are activated. OUT is an integer. When all INx where 1≤x≤16 are activated
that is = Boolean 1 it corresponds to that integer 65535 is available on the output
OUT. IB16 function is designed for receiving up to 16 booleans input locally. If the
BLOCK input is activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the
output OUT on the function block IB16.
1MRK 511 407-UEN C
Section 15
Logic
Phasor measurement unit RES670 2.2 IEC
241
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...