Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
15.14
Comparator for real inputs - REALCOMP
15.14.1
Identification
GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparator for real inputs
REALCOMP
Real<=>
15.14.2
Application
GUID-5F7B1683-9799-4D27-B333-B184F8861A5B v1
The function gives the possibility to monitor the level of real values in the system
relative to each other or to a fixed value. It is a basic arithmetic function that can be
used for monitoring, supervision, interlocking and other logics.
15.14.3
Setting guidelines
GUID-DE69FF5B-7D34-4A30-9060-214E98BFF798 v2
Setting procedure on the IED:
EnaAbs
: This setting is used to select the comparison type between signed and
absolute values.
•
Absolute
: Comparison is performed with absolute values of input and
reference.
•
Signed
: Comparison is performed with signed values of input and reference.
RefSource
: This setting is used to select the reference source between input and
setting for comparison.
•
Input REF
: The function will take reference value from input REF
•
Set Value
: The function will take reference value from setting
SetValue
Section 15
1MRK 511 407-UEN C
Logic
246
Phasor measurement unit RES670 2.2 IEC
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...