16.9
Running hour-meter TEILGAPC
16.9.1
Identification
GUID-3F9EF4FA-74FA-4D1D-88A0-E948B722B64F v1
Function Description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Running hour-meter
TEILGAPC
-
-
16.9.2
Application
GUID-225D8341-2D31-49F1-9B49-571346C0FE26 v1
The function is used for user-defined logics and it can also be used for different
purposes internally in the IED. An application example is to accumulate the total
running/energized time of the generator, transformer, reactor, capacitor bank or
even line.
Settable time limits for warning and alarm are provided. The time limit for
overflow indication is fixed to 99999.9 hours. At overflow the accumulated time
resets and the accumulation starts from zero again.
16.9.3
Setting guidelines
GUID-D3BED56A-BA80-486F-B2A8-E47F7AC63468 v1
The settings
tAlarm
and
tWarning
are user settable limits defined in hours. The
achievable resolution of the settings is 0.1 hours (6 minutes).
tAlarm
and
tWarning
are independent settings, that is, there is no
check if
tAlarm
>
tWarning
.
The limit for the overflow supervision is fixed at 99999.9 hours.
The setting
tAddToTime
is a user settable time parameter in hours.
1MRK 511 407-UEN C
Section 16
Monitoring
Phasor measurement unit RES670 2.2 IEC
279
Application manual
Summary of Contents for Relion RES670
Page 1: ...RELION 670 SERIES Phasor measurement unit RES670 Version 2 2 IEC Application manual...
Page 2: ......
Page 46: ...40...
Page 52: ...46...
Page 92: ...86...
Page 112: ...106...
Page 178: ...172...
Page 216: ...210...
Page 232: ...226...
Page 286: ...280...
Page 328: ...322...
Page 340: ...334...
Page 380: ...374...
Page 381: ...375...